Presentation Highly efficient, easy-to-deploy 10kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Includes 5x8 start-up service and 1 smart high-capacity modular battery string, expandable to 2 strings for extended runtime. |
Lead time Usually Ships within 2 Weeks |
Main |
Main Input Voltage 400 V 3 phases |
Other Input Voltage 380 V, 415 V |
Main Output Voltage 400 V 3 phases |
Other Output Voltage 380 V, 415 V |
Rated power in W 10 kW |
Rated power in VA 10 kVA |
Battery type Internal modular battery, VRLA |
Provided equipment Battery modules ship installed, Dust filter, EcoStruxure IT ready (UPS), Installation guide, Integrated network management, Power modules ship installed, Start-up service |
Range of product Galaxy VS |
Range compatibility Galaxy VS |
Batteries & Runtime |
Battery voltage 480 V |
Discharge battery voltage 384 V DC |
Max current discharge 27 A |
Battery power in VAh 0 VAh runtime |
Extended runtime 0 |
General |
Bypass voltage tolerance +/- 10 % |
Redundant No |
Product or component type Uninterruptible power supply (UPS) |
Physical |
Colour White |
Height 148.5 cm |
Width 33.3 cm |
Depth 84.7 cm |
Product weight 245 kg |
USB compatible No |
Input |
Network frequency 40...70 Hz |
Number of input connectors 1 hard wire 4-wire (3P + E), 1 hard wire 5-wire (3P + N + E) |
Input voltage limits 340...460 V 400 V |
Maximum input current 18 A |
Max short time withstand current 65 kA |
Input harmonic distortion Less than 3 % for full load |
Load power factor From 0.7 leading to 0.7 lagging without any derating |
Output |
Maximum configurable power in W 10 kW |
Harmonic distortion Less than 3 % |
Output frequency 50 Hz sync to mains, 60 Hz sync to mains, 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised, 60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised |
Crest factor 2.5 |
Wave type Sine wave |
Output voltage tolerance +/-1% after 50ms |
Output harmonic distortion < 1% linear load and < 3% non-linear load |
Output overload operation 10 minutes at 125% and 60 seconds at 150% |
Bypass type Built-in static bypass |
Maximum configurable power in VA 10 kVA |
Conformance |
Product certifications FCC part 15 class A, UL 1778 5th edition |
Standards CSA C22.2 No 107.3, EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, IEC 60721-4-2 level 2M2 |
Environmental |
Ambient air temperature for operation 0…40 °C |
Relative humidity 0…95 % non-condensing |
Operating altitude 0...3281 ft |
Ambient air temperature for storage -15…40 °C |
Storage Relative Humidity 10…80 % non-condensing |
Storage altitude 0…3048 m |
Acoustic level 55 dBA |
Heat dissipation 1240 Btu/h |
IP degree of protection IP20 |
Communications & Management |
Free slots 1 |
Control panel Touch screen LCD user interface |
Packing Units |
Unit Type of Package 1 PCE |
Number of Units in Package 1 1 |
Package 1 Height 169 cm |
Package 1 Width 99 cm |
Package 1 Length 64 cm |
Package 1 Weight 270 kg |
Contractual warranty |
Warranty 1 year on-site repair or replace with factory authorized Start-Up |
Show More